Black Box narzędzie wielofunkcyjne MPSH16-D20-120V
CHAPTER 15: Saving & Restoring Parameters
167
15. Saving and Restoring
Configuration Parameters
Once the Outlet Managed PDU is properly congured, parameters can be
downloaded and saved as an ASCII text le. Later, if the conguration is
accidentally altered, the saved parameters can be uploaded to automatically
recongure the unit without the need to manually assign each parameter.
Saved parameters can also be uploaded to other Outlet Managed PDUs, allowing
rapid set-up when several identical units will be congured with the same
parameters.
The "Save Parameters" procedure can be performed from any terminal emulation
program that allows downloading of ASCII les (e.g. HyperTerminal™,
TeraTerm©, etc.).
Note:
The Save and Restore features described in this section are only
available via the Text Interface.
15.1. Sending Parameters to a File
1. Start your terminal emulation program and access the Text Interface
command mode using an account that permits Administrator level commands.
2. When the command prompt appears, type /U and press [Enter]. The
Outlet Managed PDU will prompt you to congure your terminal emulation
program to receive an ASCII download.
a) Set your terminal emulation program to receive an ASCII download, and
the specify a name for a le that will receive the saved parameters
(e.g. psv_parameters.PAR).
b) Disable the Line Wrap function for your terminal emulation program.
This will prevent command lines from being broken in two during
transmission.