When the "Conrm Plug Actions" button is pressed, the Outlet Managed PDU
will display a screen which lists the selected action(s) and asks for conrmation
before proceeding. To implement the selected action(s), click on the "Execute Plug
Actions" button. The Outlet Managed PDU will display a screen which indicates
that a switching operation is in progress, then display the Plug Status screen when
the command is complete. At that time, the Status Screen will list the updated On/
Off status of each plug.
Notes:
When switching and reboot operations are initiated, Boot/
Sequence Delay times will be applied as described in Section 5.7.
If a switching or reboot command is directed to a plug that
is already in the process of being switched or rebooted by a
previous command, then the new command will be placed in a
queue until the plug is ready to receive additional commands.
If the Status column in the Plug Control Screen includes an
asterisk, this means that the corresponding outlet is busy
completing a previously invoked command.
When the Plug Control Screen is displayed by an account that
permits Administrator or SuperUser level commands, all switched
outlets will be displayed.
When the Plug Control Screen is displayed by a User level
account, the screen will only include the switched outlets that are
allowed by the account.